GE Multilin C60 Breaker Protection System 4-274 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE4There are several places where text messages can be programmed to allow the relay to be customized for specific applica-tions. One example is the Message Scratchpad. Use the following procedure to enter alphanumeric text messages.For example: to enter the text, “Breaker #1”.1. Press the decimal point to enter text edit mode.2. Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position.3. Repeat step 2 for the remaining characters: r,e,a,k,e,r, ,#,1.4. Press ENTER to store the text.5. If you have any problem, press HELP to view context sensitive help. Flash messages appear sequentially for severalseconds each. For the case of a text setting message, pressing HELP displays how to edit and store new values.d) ACTIVATING THE RELAYTo change the RELAY SETTINGS: "Not Programmed" mode to "Programmed", proceed as follows:1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on thedisplay.2. Press the MESSAGE RIGHT key until the SECURITY message appears on the display.3. Press the MESSAGE DOWN key until the INSTALLATION message appears on the display.4. Press the MESSAGE RIGHT key until the RELAY SETTINGS: Not Programmed message is displayed.5. After the RELAY SETTINGS: Not Programmed message appears on the display, press the VALUE keys change theselection to "Programmed".6. Press the ENTER key.7. When the "NEW SETTING HAS BEEN STORED" message appears, the relay is in "Programmed" state and the InService LED turns on.e) ENTERING INITIAL PASSWORDSThe information in this section refers to password security. For information on how to set or change CyberSentry pass-words, see the Settings > Product Setup > Security > CyberSentry section in the next chapter.RELAY SETTINGS:Not ProgrammedWhen the relay is powered up, the Trouble LED is on, the In Service LED off, and thismessage displayed, indicating the relay is in the "Not Programmed" state and is safe-guarding (output relays blocked) against the installation of a relay whose settings havenot been entered. This message remains until the relay is explicitly put in the "Pro-grammed" state.SETTINGS SETTINGS PRODUCT SETUP SECURITY DISPLAY PROPERTIES↓ INSTALLATIONRELAY SETTINGS:Not ProgrammedRELAY SETTINGS:Not ProgrammedRELAY SETTINGS:ProgrammedNEW SETTINGHAS BEEN STORED