B-46 C60 Breaker Protection System GE MultilinB.4 MEMORY MAPPING APPENDIX BB83F1 EGD Slow Producer Exchange 1 Configuration Time 0 to 4294967295 --- --- F003 083F3 EGD Slow Producer Exchange 1 Size 0 to 65535 --- 1 F001 083F4 ...Repeated for EGD Slow Producer Exchange 2EGD Fast Production (Read/Write Setting)8400 EGD Fast Producer Exchange 1 Function 0 to 1 --- 1 F102 0 (Disabled)8401 EGD Fast Producer Exchange 1 Destination 0 to 4294967295 --- 1 F003 08403 EGD Fast Producer Exchange 1 Data Rate 50 to 1000 ms 50 F001 10008404 EGD Fast Producer Exchange 1 Data Item 1 (20 items) 0 to 65535 --- 1 F001 08418 Reserved (80 items) --- --- --- F001 0EGD Slow Production (Read/Write Setting) (2 modules)8468 EGD Slow Producer Exchange 1 Function 0 to 1 --- 1 F102 0 (Disabled)8469 EGD Fast Producer Exchange 1 Destination 0 to 4294967295 --- 1 F003 0846B EGD Slow Producer Exchange 1 Data Rate 500 to 1000 ms 50 F001 1000846C EGD Slow Producer Exchange 1 Data Item 1 (50 items) 0 to 65535 --- 1 F001 0849E Reserved (50 items) --- --- --- F001 084D0 ...Repeated for EGD Exchange 2Breaker Failure (Read/Write Grouped Setting) (2 modules)8600 Breaker Failure 1 Function 0 to 1 --- 1 F102 0 (Disabled)8601 Breaker Failure 1 Mode 0 to 1 --- 1 F157 0 (3-Pole)8602 Breaker Failure 1 Source 0 to 5 --- 1 F167 0 (SRC 1)8603 Breaker Failure 1 Amp Supervision 0 to 1 --- 1 F126 1 (Yes)8604 Breaker Failure 1 Use Seal-In 0 to 1 --- 1 F126 1 (Yes)8605 Breaker Failure 1 Three Pole Initiate 0 to 4294967295 --- 1 F300 08607 Breaker Failure 1 Block 0 to 4294967295 --- 1 F300 08609 Breaker Failure 1 Phase Amp Supv Pickup 0.001 to 30 pu 0.001 F001 1050860A Breaker Failure 1 Neutral Amp Supv Pickup 0.001 to 30 pu 0.001 F001 1050860B Breaker Failure 1 Use Timer 1 0 to 1 --- 1 F126 1 (Yes)860C Breaker Failure 1 Timer 1 Pickup 0 to 65.535 s 0.001 F001 0860D Breaker Failure 1 Use Timer 2 0 to 1 --- 1 F126 1 (Yes)860E Breaker Failure 1 Timer 2 Pickup 0 to 65.535 s 0.001 F001 0860F Breaker Failure 1 Use Timer 3 0 to 1 --- 1 F126 1 (Yes)8610 Breaker Failure 1 Timer 3 Pickup 0 to 65.535 s 0.001 F001 08611 Breaker Failure 1 Breaker Status 1 Phase A/3P 0 to 4294967295 --- 1 F300 08613 Breaker Failure 1 Breaker Status 2 Phase A/3P 0 to 4294967295 --- 1 F300 08615 Breaker Failure 1 Breaker Test On 0 to 4294967295 --- 1 F300 08617 Breaker Failure 1 Phase Amp Hiset Pickup 0.001 to 30 pu 0.001 F001 10508618 Breaker Failure 1 Neutral Amp Hiset Pickup 0.001 to 30 pu 0.001 F001 10508619 Breaker Failure 1 Phase Amp Loset Pickup 0.001 to 30 pu 0.001 F001 1050861A Breaker Failure 1 Neutral Amp Loset Pickup 0.001 to 30 pu 0.001 F001 1050861B Breaker Failure 1 Loset Time 0 to 65.535 s 0.001 F001 0861C Breaker Failure 1 Trip Dropout Delay 0 to 65.535 s 0.001 F001 0861D Breaker Failure 1 Target 0 to 2 --- 1 F109 0 (Self-reset)861E Breaker Failure 1 Events 0 to 1 --- 1 F102 0 (Disabled)861F Breaker Failure 1 Phase A Initiate 0 to 4294967295 --- 1 F300 08621 Breaker Failure 1 Phase B Initiate 0 to 4294967295 --- 1 F300 08623 Breaker Failure 1 Phase C Initiate 0 to 4294967295 --- 1 F300 08625 Breaker Failure 1 Breaker Status 1 Phase B 0 to 4294967295 --- 1 F300 08627 Breaker Failure 1 Breaker Status 1 Phase C 0 to 4294967295 --- 1 F300 08629 Breaker Failure 1 Breaker Status 2 Phase B 0 to 4294967295 --- 1 F300 0862B Breaker Failure 1 Breaker Status 2 Phase C 0 to 4294967295 --- 1 F300 0862D ...Repeated for Breaker Failure 2FlexState Settings (Read/Write Setting)8800 FlexState Parameters (256 items) 0 to 4294967295 --- 1 F300 0Table B–10: MODBUS MEMORY MAP (Sheet 38 of 66)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT