GE Multilin C60 Breaker Protection System 5-495 SETTINGS 5.2 PRODUCT SETUP5The main menu for the IEC 61850 server configuration is shown below.PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL SERVER CONFIGURATIONThe IED NAME and LD INST settings represent the MMS domain name (IEC 61850 logical device) where all IEC/MMS logicalnodes are located. Valid characters for these values are upper and lowercase letters, numbers, and the underscore (_)character, and the first character in the string must be a letter. This conforms to the IEC 61850 standard. The LOCATION is avariable string and can be composed of ASCII characters. This string appears within the PhyName of the LPHD node.The IEC/MMS TCP PORT NUMBER setting allows the user to change the TCP port number for MMS connections. The INCLUDENON-IEC DATA setting determines whether or not the “UR” MMS domain will be available. This domain contains a large num-ber of UR-series specific data items that are not available in the IEC 61850 logical nodes. This data does not follow the IEC61850 naming conventions. For communications schemes that strictly follow the IEC 61850 standard, this setting should be“Disabled”.When a 0 value is involved in a change, the changes to the IEC/MMS TCP PORT NUMBER setting take effect when theC60 is restarted.Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation ofthose protocols.The SERVER SCANNING feature should be set to “Disabled” when IEC 61850 client/server functionality is not required. IEC61850 has two modes of functionality: GOOSE/GSSE inter-device communication and client/server communication. If theGOOSE/GSSE functionality is required without the IEC 61850 client server feature, then server scanning can be disabledto increase CPU resources. When server scanning is disabled, there is no updating of the IEC 61850 logical node statusvalues in the C60. Clients are still able to connect to the server (C60 relay), but most data values are not updated. This set-ting does not affect GOOSE/GSSE operation.Changes to the IED NAME setting, LD INST setting, and GOOSE dataset take effect when the C60 is restarted. SERVER CONFIGURATIONIED NAME: IECDevice Range: up to 32 alphanumeric charactersMESSAGE LD INST: LDInst Range: up to 32 alphanumeric charactersMESSAGE IEC/MMS TCP PORTNUMBER: 102Range: 0 to 65535 in steps of 1MESSAGE INCLUDE NON-IECDATA: EnabledRange: Disabled, EnabledMESSAGE SERVER SCANNING:DisabledRange: Disabled, EnabledMESSAGE LOCATION: LPHD DC PHV-Nam LocationRange: up to 80 alphanumeric charactersMESSAGE LATITUDE: Range: -90.000 to 90.000 deg in steps of 0.001 degMESSAGE LONGITUDE: Range: -180.000 to 180.000 deg in steps of 0.001 degMESSAGE ALTITUDE: Range: 0 to 10,0000 m in steps of 1 mNOTENOTE