5-220 C60 Breaker Protection System GE Multilin5.7 CONTROL ELEMENTS 5 SETTINGS55.7.6 AUTORECLOSE (ANSI 79)PATH: SETTINGS CONTROL ELEMENTS AUTORECLOSE AUTORECLOSE AUTORECLOSEAR FUNCTION:DisabledRange: Disabled, EnabledMESSAGE AR MODE:Mode 1 (1 & 3 Pole)Range: Mode 1(1 & 3 Pole), Mode 2 (1 Pole), Mode 3 (3Pole-A), Mode 4 (3 Pole-B)MESSAGE Mode 1 Activation:OffRange: FlexLogic operandMESSAGE Mode 2 Activation:OffRange: FlexLogic operandMESSAGE Mode 3 Activation:OffRange: FlexLogic operandMESSAGE Mode 4 Activation:OffRange: FlexLogic operandMESSAGE AR MAX NUMBER OFSHOTS: 2Range: 1, 2, 3, 4MESSAGE AR INITIATE MODE:Protection AND CBRange: Protection AND CB, Protection OnlyMESSAGE AR BLOCK BKR1:OffRange: FlexLogic operandMESSAGE AR CLOSE TIME BKR 1:0.10 sRange: 0.00 to 655.35 s in steps of 0.01MESSAGE AR BKR MAN CLOSE:OffRange: FlexLogic operandMESSAGE AR BLK TIME UPON MANCLS: 10.00 sRange: 0.00 to 655.35 s in steps of 0.01MESSAGE AR 1P INIT:OffRange: FlexLogic operandMESSAGE AR 3P INIT:OffRange: FlexLogic operandMESSAGE AR 3P TD INIT:OffRange: FlexLogic operandMESSAGE AR MULTI-P FAULT:OffRange: FlexLogic operandMESSAGE BKR ONE POLE OPEN:OffRange: FlexLogic operandMESSAGE BKR 3 POLE OPEN:OffRange: FlexLogic operandMESSAGE AR 3-P DEAD TIME 1:0.50 sRange: 0.00 to 655.35 s in steps of 0.01MESSAGE AR 3-P DEAD TIME 2:1.20 sRange: 0.00 to 655.35 s in steps of 0.01MESSAGE AR 3-P DEAD TIME 3:2.00 sRange: 0.00 to 655.35 s in steps of 0.01