2-26 C60 Breaker Protection System GE Multilin2.4 SPECIFICATIONS 2 PRODUCT DESCRIPTION22.4.8 COMMUNICATION PROTOCOLSRS232Front port: 19.2 kbps, Modbus RTURS4851 rear port: Up to 115 kbps, Modbus RTU, DNP 3,IEC 60870-5-103Typical distance: 1200 mIsolation: 2 kV, isolated together at 36 VpkFIBER ETHERNET PORTETHERNET (10/100 MB TWISTED PAIR)Modes: 10 MB, 10/100 MB (auto-detect)Connector: RJ45SIMPLE NETWORK TIME PROTOCOL (SNTP)clock synchronization error: <10 ms (typical)PRECISION TIME PROTOCOL (PTP)PTP IEEE Std 1588 2008 (version 2)Power Profile (PP) per IEEE Standard PC37.238TM2011Slave-only ordinary clockPeer delay measurement mechanismPARALLEL REDUNDANCY PROTOCOL (PRP)(IEC 62439-3 CLAUSE 4, 2012)Ethernet ports used: 2 and 3Networks supported: 10/100 MB EthernetOTHERTFTP, HTTP, IEC 60870-5-104, Ethernet Global Data (EGD)2.4.9 INTER-RELAY COMMUNICATIONSSHIELDED TWISTED-PAIR INTERFACE OPTIONSRS422 distance is based on transmitter power anddoes not take into consideration the clock sourceprovided by the user.LINK POWER BUDGET AND MAXIMUM OPTICAL INPUT POWERPARAMETER FIBER TYPE100 MB MULTI-MODEWavelength 1310 nmConnector LCTransmit power –20 dBmReceiver sensitivity –30 dBmPower budget 10 dBMaximum inputpower–14 dBmTypical distance 2 kmFull duplex yesRedundancy yesINTERFACE TYPE TYPICAL DISTANCERS422 1200 mG.703 100 mNOTE