GE Multilin C60 Breaker Protection System B-75APPENDIX B B.4 MEMORY MAPPINGBB.4.2 DATA FORMATSF001UR_UINT16 UNSIGNED 16 BIT INTEGERF002UR_SINT16 SIGNED 16 BIT INTEGERF003UR_UINT32 UNSIGNED 32 BIT INTEGER (2 registers)High order word is stored in the first register.Low order word is stored in the second register.F004UR_SINT32 SIGNED 32 BIT INTEGER (2 registers)High order word is stored in the first register.Low order word is stored in the second register.F011UR_UINT16 FLEXCURVE DATA (120 points)A FlexCurve is an array of 120 consecutive data points (x, y) thatare interpolated to generate a smooth curve. The y-axis is theuser-defined trip or operation time setting; the x-axis is the pickupratio and is pre-defined. See format F119 for a listing of the pickupratios; the enumeration value for the pickup ratio indicates the off-set into the FlexCurve base address where the corresponding timevalue is stored.F013POWER_FACTOR (SIGNED 16 BIT INTEGER)Positive values indicate lagging power factor; negative valuesindicate leading.F050UR_UINT32 TIME and DATE (UNSIGNED 32 BIT INTEGER)Gives the current time in seconds elapsed since 00:00:00 January1, 1970.F051UR_UINT32 DATE in SR format (alternate format for F050)First 16 bits are Month/Day (MM/DD/xxxx).Month: 1=January, 2=February,...,12=December.Day: 1 to 31 in steps of 1.Last 16 bits are Year (xx/xx/YYYY): 1970 to 2106 in steps of 1.F052UR_UINT32 TIME in SR format (alternate format for F050)First 16 bits are Hours/Minutes (HH:MM:xx.xxx).Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm.Minutes: 0 to 59 in steps of 1.Last 16 bits are Seconds (xx:xx:.SS.SSS): 0=00.000s,1=00.001,...,59999=59.999s).F060FLOATING_POINT IEEE FLOATING POINT (32 bits)F072HEX6 6 BYTES - 12 ASCII DIGITSF073HEX8 8 BYTES - 16 ASCII DIGITSF074HEX20 20 BYTES - 40 ASCII DIGITSF081ENUMERATION: AUTORECLOSE 1P/3P BKR FAIL OPTION0 = Continue, 1 = LockoutF082ENUMERATION: AUTORECLOSE SINGLE-PHASE /THREE-PHASE (1P 3P) BREAKER SEQUENCE0 = 1, 1 = 2, 2 = 1 & 2, 3 = 1 – 2, 4 = 2 – 1F083ENUMERATION: SELECTOR MODES0 = Time-Out, 1 = AcknowledgeF084ENUMERATION: SELECTOR POWER UP0 = Restore, 1 = Synchronize, 2 = Sync/RestoreF086ENUMERATION: CONTACT INPUT DEFAULT STATE0 = Off, 1 = On, 2= Latest/Off, 3 = Latest/OnF090ENUMERATION: LATCHING OUTPUT TYPE0 = Operate-dominant, 1 = Reset-dominantF100ENUMERATION: VT CONNECTION TYPE0 = Wye, 1 = Delta