CHAPTER 4: INTERFACES FRONT PANEL INTERFACEL60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL 4-354Properties that can be edited include alarm type (acknowledgeable, latched, self-reset), alarm input (any FlexLogicoperand), text color, and alarm background color.The following buttons display at the top of the window:• Save — Updates the connected device if online or the open setting file if offline with changes made• Restore — Undoes changes that have not been saved• Default — Changes all annunciator settings to their factory default values• Reset — Displays factory default values. Previous settings are not lost unless you save the reset window.Metering editorThe metering editor is an actual values display tool. It creates pages of actual values for the graphical front panel. Thereare two types: tables and phasor diagrams. Tabular actual values pages have settings to configure, while phasor actualvalues pages have no settings. Five tabular metering pages can be configured, while there can be a phasor page for eachconfigured AC source. They display on the graphical front panel using the Metering Tab pushbutton.The path to the editor is Settings > Product Setup > Graphical Panel > Metering Editor.Figure 4-44: Metering editor with preview windowThe inputs are selected at the top. Select from the drop-down list or start typing in the field.The page, page name, and grid layout are set below the inputs.Content to display is configured with the cell lines. The content can be actual values, a status indicator, or text.• Actual value — Select from the FlexAnalogs applicable to the L60, where a FlexAnalog is an analog parameter