CHAPTER 5: SETTINGS GROUPED ELEMENTSL60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL 5-2635Figure 5-145: Neutral directional overcurrent logic5.6.10 Wattmetric ground fault5.6.10.1 Wattmetric zero-sequence directional (ANSI 32N, IEC PSDE)SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) WATTMETRIC... WATTMETRIC GROUND FAULT 1(2) WATTMETRIC GROUND FAULT 1 WATTMETRIC GND FLT 1FUNCTION: DisabledRange: Disabled, Enabled WATTMETRIC GND FLT 1SOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4 WATTMETRIC GND FLT 1VOLT: Calculated VNRange: Calculated VN, Measured VX WATTMETRIC GND FLT 1OV PKP: 0.20 puRange: 0.02 to 3.00 pu in steps of 0.01 WATTMETRIC GND FLT 1CURR: Calculated INRange: Calculated IN, Measured IG WATTMETRIC GND FLT 1OC PKP: 0.060 puRange: 0.002 to 30.000 pu in steps of 0.001