5-286 L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUALGROUPED ELEMENTS CHAPTER 5: SETTINGS55.6.14 Voltage elements5.6.14.1 MenuSETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) VOLTAGE ELEMENTSThese protection elements can be used for a variety of applications, such as• Undervoltage protection — For voltage sensitive loads, such as induction motors, a drop in voltage increases thedrawn current, which can cause dangerous overheating in the motor. The undervoltage protection feature can beused to either cause a trip or generate an alarm when the voltage drops below a specified voltage setting for aspecified time delay.• Permissive functions — The undervoltage feature can be used to block the functioning of external devices byoperating an output relay when the voltage falls below the specified voltage setting. The undervoltage feature canalso be used to block the functioning of other elements through the block feature of those elements.• Source transfer schemes — In the event of an undervoltage, a transfer signal can be generated to transfer a loadfrom its normal source to a standby or emergency power source.The undervoltage elements can be programmed to have a definite time delay characteristic. The definite time curveoperates when the voltage drops below the pickup level for a specified period of time. The time delay is adjustable from 0to 600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delaycharacteristic. VOLTAGE ELEMENTS PHASE UNDERVOLTAGE1See below PHASE UNDERVOLTAGE3 PHASE OVERVOLTAGE1See page 5-288 PHASE OVERVOLTAGE3 NEUTRAL OV1See page 5-289 NEUTRAL OV3 NEG SEQ OV1See page 5-290 NEG SEQ OV3 AUXILIARY UV1See page 5-291 AUXILIARY UV3 AUXILIARY OV1See page 5-292 COMPENSATED OVERVOLTAGESee page 5-293