CHAPTER 5: SETTINGS GROUPED ELEMENTSL60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL 5-2815BF1 PH AMP LOSET PICKUP — This setting sets the phase current output supervision level. Generally this setting is to detectthe lowest expected fault current on the protected breaker, after a breaker opening resistor is inserted (approximately 90%of the resistor current).BF1 N AMP LOSET PICKUP — This setting sets the neutral current output supervision level. Generally this setting is to detectthe lowest expected fault current on the protected breaker, after a breaker opening resistor is inserted (approximately 90%of the resistor current). This setting is valid only for three-pole breaker failure schemes.BF1 LOSET TIME DELAY — Sets the pickup delay for current detection after opening resistor insertion.BF1 TRIP DROPOUT DELAY — This setting is used to set the period of time for which the trip output is sealed-in. This timermust be coordinated with the automatic reclosing scheme of the failed breaker, to which the breaker failure element sendsa cancel reclosure signal. Reclosure of a remote breaker can also be prevented by holding a transfer trip signal on longerthan the reclaim time.BF1 PH A INITIATE / BF1 PH B INITIATE / BF 1 PH C INITIATE — These settings select the FlexLogic operand to initiate phase A, B,or C single-pole tripping of the breaker and the phase A, B, or C portion of the scheme, accordingly. This setting is only validfor single-pole breaker failure schemes.BF1 BKR POS1 φB / BF1 BKR POS 1 φC — These settings select the FlexLogic operand to represents the protected breakerearly-type auxiliary switch contact on poles B or C, accordingly. This contact is normally a non-multiplied Form-A contact.The contact can even be adjusted to have the shortest possible operating time. This setting is valid only for single-polebreaker failure schemes.BF1 BKR POS2 φB — Selects the FlexLogic operand that represents the protected breaker normal-type auxiliary switchcontact on pole B (52/a). This can be a multiplied contact. This setting is valid only for single-pole breaker failure schemes.BF1 BKR POS2 φC — This setting selects the FlexLogic operand that represents the protected breaker normal-type auxiliaryswitch contact on pole C (52/a). This can be a multiplied contact. For single-pole operation, the scheme has the sameoverall general concept except that it provides re-tripping of each single pole of the protected breaker. The approachshown in the following single pole tripping diagram uses the initiating information to determine which pole is supposed totrip. The logic is segregated on a per-pole basis. The overcurrent detectors have ganged settings. This setting is valid onlyfor single-pole breaker failure schemes.Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command needs to begiven via output operand BKR FAIL 1 TRIP OP.