5-168 L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUALFLEXLOGIC CHAPTER 5: SETTINGS5Table 5-21: L60 FlexLogic operandsOperand type Operand syntax Operand descriptionANNUNCIATORGraphical front panelANY ANCTR ABNORMALANY ANCTR ALARMEDOn for one second when any annunciator window state changes fromnormal to abnormalOn while any annunciator window state is abnormalCONTROLPUSHBUTTONSEnhanced andstandard front panelsCONTROL PUSHBTN 1 ONCONTROL PUSHBTN 2 ONCONTROL PUSHBTN 3 ONCONTROL PUSHBTN 4 ONCONTROL PUSHBTN 5 ONCONTROL PUSHBTN 6 ONCONTROL PUSHBTN 7 ONControl pushbutton 1 is being pressedControl pushbutton 2 is being pressedControl pushbutton 3 is being pressedControl pushbutton 4 is being pressedControl pushbutton 5 is being pressedControl pushbutton 6 is being pressedControl pushbutton 7 is being pressedCYBERSENTRY ROLE ADMIN ACTROLE SUPERVISOR ACTROLE ENGINEER ACTROLE OPERATOR ACTROLE OBSERVER ACTAUTHENTICATION FAILUNAUTH FW ATTEMPTUNAUTH SETTING WRITEAdministrator role is active and is set to true when that is the caseSupervisor role is active and is set to true when that is the caseEngineer role is active and is set to true when that is the caseOperator role is active and is set to true when that is the caseObserver role is active and is set to true when that is the caseOperand set for Failed Authentication self-test and alarmOperand set for firmware lock self-test and alarmOperand set for settings lock self-test and alarmDIRECT INPUT/OUTPUT CHANNELMONITORINGDIR IO CH1 CRC ALARMDIR IO CH2 CRC ALARMDIR IO CH1 UNRET ALMDIR IO CH2 UNRET ALMThe rate of direct input messages received on channel 1 and failing the CRCexceeded the user-specified levelThe rate of direct input messages received on channel 2 and failing the CRCexceeded the user-specified levelThe rate of returned direct input/output messages on channel 1 exceededthe user-specified level (ring configurations only)The rate of returned direct input/output messages on channel 2 exceededthe user-specified level (ring configurations only)ELEMENT:87PC phasecomparison87PC PKP87PC OP87PC DPO87PC TRANS BLOCK OP87PC FDL OP87PC FDH OP87PC BKR ECHO PKP87PC V2 FDL OP87PC V2 FDH OP87PC dI2/dt FDL OP87PC dI2/dt FDH OP87PC dI1/dt FDL OP87PC dI1/dt FDH OP87PC I_2 FDL OP87PC I_2 FDH OP87PC I_1 FDL OP87PC I_1 FDH OP87PC RX187PC RX2Phase comparison has picked upPhase comparison has operatedPhase comparison has dropped outPhase comparison transient blocking has operatedOvercurrent fault detector low has operatedOvercurrent fault detector high has operatedOpen breaker echo of phase comparison has picked upAdvanced fault detector low, I2*Z - V2 has operatedAdvanced fault detector high, I2*Z - V2 has operatedAdvanced fault detector low, rate of change of the negative-sequencecurrent has operatedAdvanced fault detector high, rate of change of the negative -sequencecurrent has operatedAdvanced fault detector low, rate of change of the positive-sequence currenthas operatedAdvanced fault detector high, rate of change of the positive-sequencecurrent has operatedAdvanced fault detector low, negative-sequence current has operatedAdvanced fault detector high, negative-sequence current has operatedAdvanced fault detector low, positive-sequence current has operatedAdvanced fault detector high, positive-sequence current has operatedReceived pulse on channel 1Received pulse on channel 2