REV CSection 4 • Repair ProceduresJune 2005Part No. 52075 TMZ-34/19 4 - 275-6Level SensorOne level sensor monitors the incline of theturntable after the outriggers are deployed and themachine is level. The Electronic Control Module(ECM) is programmed to deactivate lift functionsand activate an alarm when a signal is receivedfrom the level sensor, making the operator awareof a potentially hazardous situation.The tilt alarm sounds when the incline of thechassis exceeds 1.5° in any direction. The tilt levelsensor is located below the ground control box.How to Install and Calibrate theTilt Level SensorTip-over hazard. Failure to installor calibrate the level sensor asinstructed could result in themachine tipping over causingdeath or serious injury. Do notinstall or calibrate the level sensorother than specified in thisprocedure.1 Perform this procedure with the machine on afirm, level surface that is free of obstructions.2 Turn the key switch to ground control and pullout the red Emergency Stop button to the onposition at both the ground and platformcontrols.Result: The power light should be on.Models with hydraulic outriggers:3 Push and hold the auto level button. Push andhold the extend outrigger button.Result: The outriggers will lower and adjust tolevel the machine and raise the wheels slightlyoff the ground. Use a digital level to confirm thatthe machine is level.Models with manual outriggers:4 Lower and lock into place each outrigger.5 Adjust the outriggers to level the machine andraise the wheels slightly off the ground.Result: The corresponding interlock displaylights will be on. If the light is flashing, continueadjusting the outrigger until the light remainson.All models:6 Turn the key switch to the off position.7 Locate the tilt level sensor next to the groundcontrol box.XYabca battery chargerb ground control boxc level sensorGROUND CONTROLS800-610-4101ActionRental.com