© 2017 MA Lighting Technology GmbH | Dachdeckerstr. 16 | D-97297 Waldbüttelbrunn | GermanyPhone +49 5251 688865-30 | tech.support (at)malighting.com | www.malighting.comVersion 3.3Information:The Ethernet port 2 can be used for the following network protocols:- Art-Net- CITPInformation:The IP address is set by default in a 2.x.x.x range. An IP address is required in a 2.x.x.x or 10.x.x.x rangefor Art-Net.Requirement:STP (shielded twisted pair) cable with RJ45 connector, min. Cat 5e.To connect Ethernet port 2:1. Connect one end of a Ethernet cable to the Ethernet 2 port.2. Connect the other end to a suitable switch.3. Connect other grandMA2 equipment to the switch and turn on the power on the switch.Ethernet is connected to port 2.5.12. Connect Analog Remote ControlTo use the analog remote control, connect a contact closure switch e.g., a light barrier or a push button.Generate a switch that sends between +5 and +15 volts to pin 1 for the console to react to analog input number 1.There are two ways to generate a switch:1. Take the +5V voltage from pin 21-22.-or-2. Take an external voltage (+5V up to +15V), connect the ground of the external voltage source to thecommon ground pin of the grandMA2 console or MA onPC command wing.Then connect the switch to one input pin 1-16 with a potential free contact (switcher, buzzer, motion detector, orany other switching device) in between.To configure the remote see Remote Controlling the System - Remote Input.Pin layout for grandMA2 consoles:The grandMA2 consoles have a 25 pin D-sub, enabling 16 remote inputs:Pin 1-16 = inputPin 21-22 = + 5VPin 25 = common ground49