Special Zone Outputs Coding Functions for Panel Circuit Outputs104 NFS-3030 Programming Manual P/N 51345:C 11/4/03Selecting Presignal and PAS OutputsPresignalThe Presignal Delay Timer can be set to a value between 60 and 180 seconds. A Presignal DelayTimer does not apply to the following:•System Alarm relay•TM-4 polarity reversal alarm output•TM-4 municipal box output•UDACTPositive Alarm Sequence (PAS)Outputs selected for PAS delay for 15 seconds. Acknowledgement within the 15-second delay willset the Presignal Delay Timer to the full programmed value (60-180 seconds, including the PASdelay of 15 seconds). When an alarm comes from an initiating device with a CBE list that includesZF0, the control panel delays the following outputs:•System Alarm relay•TM-4 polarity reversal alarm output•TM-4 municipal box output•UDACTC.2 Coding Functions for Panel Circuit OutputsCoding Functions are selectable pulsed signals that energize Panel Circuit outputs when a firealarm occurs.Note: Do not include ZF8 in the zone map of Panel Circuits used for releasing or zone coding applications.Select Coding Functions on a global basis by setting the Panel Circuit Bell Coding field to Marchor Temporal. (Refer to “Panel Settings (2) Screen” on page 20). Select individual panel circuitoutput points for coding participation by entering ZF8 in the point’s zone map. All Panel Circuitoutputs with ZF8 in their zone maps will sound the same code when activated. The table belowcontains descriptions of each Coding Function selection:Appendix Table C-1 Coding Function SelectionsCoding FunctionSelection SignalMarch Time (default) 120 PPM (pulses per minute)Temporal 0.5s on, 0.5s off, 0.5s on, 0.5s off, 0.5s on, 1.5s off, repeatswww.PDF-Zoo.com