Panel Program ProgramNFS-3030 Programming Manual P/N 51345:C 11/4/03 27SOURCE: Pressing this soft key will select the Source field and also toggle between displayformats if a point value is allowed. Enter a point or zone, or the panel’s node number if the modetype is a system function such as acknowledge or reset.Up to eight sources are allowed when CONTROL mode is chosen.ACCEPT: Press this soft key to save the changes to the point displayed. The next point address willappear.BACK: Press this soft key to exit the screen without saving, and return to the ACS ProgrammingScreen.3.2.8 SupervisionFrom the Panel Program Menu (1), select SUPERVISION to display the following screen.Figure 3.12 Supervision ScreenSoft KeysMAIN POWER SUPPLY AC FAIL ADDRESS: Press to enter the “Monitor AC Fail” (base plusone) address of the main power supply. Refer to the main power supply manual for completeaddressing information. Type in the address using the keypad.The LCD backlight will turn off when this power supply experiences AC failure (see BACKLIGHTin "LCD Programming" on page 23).PRINTER: Press to scroll through the types of printer supervision: NONE, 40-COLUMN,40-COLUMN SUPERVISED, 80-COLUMN, 80-COLUMN SUPERVISED, GRAPHIC, ORGRAPHIC SUPERVISED. The printer will not be active if NONE is selected. If a SUPERVISEDselection is made, the printer will be supervised. Default: NONENote: When changing from an 80-column or 80-column supervised to a graphic or graphicsupervised printer (or vice-versa) , settings must be changed at the printer. Refer to this panel’sinstallation manual for the settings.AUXILIARY TROUBLE REPORTING: Press to toggle between Yes and No. Choose Yes if atrouble bus cable has been attached at J5 of the CPU-3030. Default: NOTAMPER INPUT: Press the soft key to toggle between Yes, No, and AKS-1.Yes/No reports (YES) or does not report (NO) a tamper situation at the panel cabinet door (asdetermined by an STS-1 tamper switch connected as shown in this panel’s installationmanual).AKS-1 should be selected when there is an AKS-1 key switch connected to the panel cabinetdoor (which allows the operator to use Signal Silence, Reset, Drill and Acknowledge functionswhen a key turns the lock to “Enable”). Default: NOS U P E R V I S I O NM A I N P S A C F A I L A D D R E S S : L X X M X X XP R I N T E R : 8 0 - C O L U M NA U X I L I A R Y T R O U B L E R E P O R T I N G : N O A C C E P TT A M P E R I N P U T : N O B A C Kwww.PDF-Zoo.com