Program Panel Program24 NFS-3030 Programming Manual P/N 51345:C 11/4/03backlight on or off.Figure 3.9 LCD Display ScreenSoft KeysBRIGHTER: Press this soft key to increase contrast. The intensity will increase by approximately5% with each press of the key.DARKER: Press this soft key to decrease contrast. The intensity will decrease by approximately5% with each press of the key.LANGUAGE: Press this soft to choose the language that will display on the LCD. Menu choices areENGLISH, HEBREW, PORTUGUESE and SPANISH.To change the language display on an LCD-160, refer to "LCD-160 Download Menu" on page 73.BACKLIGHT: Press this soft key to select one of the following backlighting options: ON EXCEPTAC FAIL, OFF, or ON. When ON EXCEPT AC FAIL is selected, the backlight will turn off whenthe power supply designated as the main power supply experiences AC failure. (The designation ismade at the Supervision screen using the MAIN POWER SUPPLY AC FAIL ADDRESS field. Referto "Supervision" on page 27.)Default: ONDEFAULT: Press to select the factory default setting (60%).CURRENT:Press to select the intensity that was in effect when the screen was accessed..ACCEPT: Line 5 (which displays LCD INTENSITY: 50% in the figure above) will changevalue when the INTENSITY soft keys are pressed. Press ACCEPT to save the desired setting.3.2.7 ACS ProgrammingAn ACS device is a remote device used by the panel to annunciate certain system messages, and/orto act with limited commands. A total of 32 annunciator devices may be present on the EIA-485ACS circuit; however, some devices have associated expander devices, and an NFS-3030/E ACScircuit can accomodate up to 3,072 annunciator points. The ACS Programming and ACS PointProgramming screens in this section allow the user to define the mapping and functional mode ofthese devices and points. Each annunciator board may be labeled using the ACS Label Menu.(Refer to “Annunciator Board Label” on page 51).Note: Smoke Control devices must be set as FSCS or HVAC annunciator types. In addition to its 64smoke control points, when an SCS device is operating in FSCS (Firefighters Smoke ControlStation) mode, there are 32 additional points which function as alarm points. They can be mappedto a zone or point to send the SCS device into a fire alarm state when any of the additional 32 pointsis activated. Any of the 32 alarm points that are used must be set to MONITOR mode from thepanel. Any of these points that are not used can be set to NONE. Refer to the SCS manual forfurther information on Smoke Control devices.L C D P R O G R A M M I N GL C D I N T E N S I T Y : 5 0 %B R I G H T E R D E F A U L TD A R K E R C U R R E N TL A N G U A G E : E N G L I S H A C C E P TB A C K L I G H T O N E X C E P T A C F A I L B A C Kwww.PDF-Zoo.com