Abort Switches Releasing ApplicationsNFS-3030 Programming Manual P/N 51345:C 11/4/03 97How to Program a Release CircuitNote: A Release Circuit with this Type Code requires the following selections: a Releasing Zone; an output circuitmapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No Walk Test.Note: Do not use a Release Circuit for the following: An application requiring ULC Listing; An applicationrequiring power-limited energy cable.The following contains information needed to program a Release Circuit for an SLC output circuitmodule .Description An SLC output module used to activate a releasing solenoid or other releasingdevice. Multiple outputs with the RELEASE CKT Type Code can be mapped to thesame Releasing Zone. When the Releasing Zone activates, all outputs associatedwith the releasing zone and with the RELEASE CKT Type Code also activate at thesame time. A Release Circuit activates when:• An initiating device programmed to the same Releasing Zone activates (twodevices if using the Cross Zone option)• The Delay Timer for the releasing zone (if used) expires• The Abort Switch for the releasing zone (if used) is not activeProgram Select an SLC output module to use as a Release Circuit. While programming thepoint (refer to the Point Programming section of this manual for instructions),1. Select the RELEASE CKT Type Code2. Enter the number of the desired Releasing Zone into the module’s zone map.The releasing zone must be fully programmed (refer to "Releasing Zone" onpage 46).Example A programming example of a control module programmed as a Release Circuit for ReleasingZone ZR05.Appendix Figure B-16 Output Module Configured as a Release CircuitType CodeRELEASE CKTZR05MonitorModule Detector Detector DetectorType CodeRELEASE CKTFor example, all modules programmed with the RELEASE CKTType Code activate simultaneously with other outputs (modules A& B) programmed for ZR05.SLCoutputmoduleSLCoutputmoduleASLCoutputmoduleBSLCoutputmodulewww.PDF-Zoo.com