Type Codes Type Codes for Output Devices126 NFS-3030 Programming Manual P/N 51345:C 11/4/03G.4 Type Codes for Output DevicesThis section provides a list of Type Codes for SLC control module points and panel circuit outputmodule points. Select from these codes to define the type of pointNote: Do not assign Releasing Type Codes to panel circuit module points.Appendix Table G-3 SLC Control Module and Panel Circuit Output Module Type CodesType CodeSilenceable(Y=yesN=no)*SwitchInhibit(Y=yes,N=No)*WalkTest(Y=yes,N=No)*SLC or Panel CircuitOutput Point Device FunctionCONTROL Y N Y NAC Supervised NACRELAY Y N Y Relay Relay outputBELL CIRCUIT Y N Y NAC Supervised NACSTROBE CKT Y N Y NAC Supervised NACHORN CIRCUIT Y N Y NAC Supervised NACAUDIBLE CKT Y N Y NAC Supervised NACSPEAKER Y N Y NAC Supervised NAC for speaker circuitsblank Y N Y NAC Supervised NAC for undefined deviceNONRESET CTL N N N Relay or NAC Supervised output, unaffected by “System Reset” commandTELEPHONE N N N Relay Supervised Telephone circuitCONTROL NAC Y N Y NAC Supervised NACISOLATED NAC Y N Y NAC Supervised NAC for notification appliance, used with audioisolators. Activates even if there is a short on its NAC circuit.For ULC installations only.ISOLATED SPK Y N Y NAC Supervised NAC for speaker circuits, used with audio isolators.Activates even if there is a short on its audio circuit. For ULCinstallations only.GEN ALARM N Y Y NAC Control Module, XPC-8, or an XP5-C (in NAC mode) configured asa Municpal Box Transmitter for NFPA 72 Auxiliary Fire AlarmSystems applications (MBT-1 required). This Type ID can also beused for general alarm activation.GEN SUPERVIS N Y Y NAC Control Module, XPC-8, or an XP5-C (in NAC mode) activatedunder any Supervisory condition (includes sprinkler type).GEN TROUBLE N Y Y NAC Control Module, XPC-8, or an XP5-C (in NAC mode) activatedunder any System Trouble condition.This device will not turn ONwhen it is in trouble (short or open).GENERAL PEND N Y Y NAC Control Module XPC-8 circuit, or an XP5-C (in NAC mode) thatwill activate upon receipt of an alarm and/or trouble condition,and remain in the ON state until all events have beenACKNOWLEDGED. This device will not turn ON when it is introuble (short or open)TROUBLE PEND N Y Y NAC Control Module or an XP5-C (in NAC mode) that will activate uponreceipt of a trouble condition, and remain in the ON state until alltroubles have been ACKNOWLEDGED. This device will not turnON when it is in trouble (short or open).ALARMS PEND N Y Y NAC Control module/panel circuit or NAC for output that willactivate upon receipt of an alarm condition, and remain in thealarm state until all alarms have been acknowledged.INST RELEASE N Y N NAC (SLC only) Supervised for open circuits and ground faults. Short = normalREL. FORM C N Y N Form-C relay (SLC only) Directs relay outputs to perform a releasing function.RELEASE CKT N Y N NAC (SLC only) Directs outputs to perform a releasing function.REL CKT ULC N Y N NAC (SLC only) Directs outputs to perform a release function as required byULC.REL END BELL N Y N NAC Activates NAC audio or visual device when releasing circuitsshut off.REL AUDIBLE Y Y N NAC Activates audio or visual devices steady when releasing starts.FORM C RESET N Y N Form-C Relay (SLC only) Control module used to interrupt 24V power to four-wireconventional detectors for 30 seconds upon reset. Used inconjunction with a monitor module with a conventional detectorType ID* Values represent program defaults.www.PDF-Zoo.com