Type Codes for Input Devices Type CodesNFS-3030 Programming Manual P/N 51345:C 11/4/03 125Type Codes for Monitor ModulesNote: A list of monitor module Type Codes, which you can use to change the function of a monitormodule point.Note: Do not assign Releasing Type Codes to Panel Circuit module points.Appendix Table G-2 Type Codes for Monitor ModulesType CodePointCharacteristicsDevice FunctionPoint Type Latching(Y=yesN=no)ActivatesCBEMONITOR fire alarm Y Y Alarm-monitoring devicePULL STATION fire alarm Y Y Manual fire-alarm-activating deviceSMOKE CONVEN fire alarm Y Y Indicates activation of a conventional smoke detector. An FZM-1 must be used foralarm verification of a two-wire conventional detector.SMOKE DETECT fire alarm Y Y Indicates activation of a conventional smoke detector. An FZM-1 must be used foralarm verification of a two-wire conventional detectorWATERFLOW fire alarm Y Y Monitor for waterflow alarm switchWATERFLOW S supervisory Y Y Indicates supervisory condition for activated waterflow switchACCESS MONTR non-alarm security N Y Used for monitoring building accessAREA MONITOR security Y Y Monitors building accessAUDIO SYSTEM trouble N N Used for monitoring audio equipment (use trouble zones for activations)EQUIP MONITR non-alarm security N Y Used for monitoring equipmentSECURITY L security Y Y Indicates activation of security alarmLATCH SUPERV supervisory Y Y Indicates latching supervisory conditionTRACK SUPERV supervisory N Y Monitors for waterflow tamper switches for alarm pointsSPRINKLR SYS supervisory Y Y Monitors a waterflow deviceSYS MONITOR security Y Y Monitors equipment securityTAMPER supervisory Y Y Indicates activation of tamper switchACK SWITCH non-alarm N N Emulates panel Acknowledge switchALLCALL PAGE non-alarm N Y Emulates AMG-1 All-call switch and telephone pageDRILL SWITCH non-alarm N N Emulates panel Drill switch, activates silenceable fire outputsEVACUATE SWITCH non-alarm N N Emulates panel Drill Switch, activates silenceable fire outputsFIRE CONTROL non-alarm N Y Monitors non-fire activationsNON FIRE non-alarm N Y Monitors non-fire activationsPAS INHIBIT non-alarm N N Inhibits Positive Alarm SequencePOWER MONITR trouble N N Monitors main and auxiliary power supplies (use trouble zones for activations)RESET SWITCH non-alarm N N Emulates keypad Reset switchSIL SWITCH non alarm N N Emulates keypad Signal Silence switchTELE PAGE non-alarm N Y Emulates Page Button on FFT-7. Allows remote paging to a fire areaTROUBLE MON trouble N N Monitors trouble inputs (use trouble zones for activations)Blank fire alarm Y Y Monitors for a device with no descriptionHEAT DETECT fire alarm Y Y Monitors for conventional heat detectorRF MON MODUL fire alarm Y Y Wireless alarm-monitoring deviceRF PULL STA fire alarm Y Y Wireless manual fire-alarm-activating deviceRF SUPERVSRY supervisory N Y Wireless supervisory-monitoring deviceABORT SWITCH non-alarm N Y Provides an abort function through a monitor module (connected to a UL-listedabort station) for a releasing zone.MAN RELEASE fire alarm Y Y Provides a manual release through a monitor module (connected to a UL-listed pullstation) for a releasing zoneMAN REL DELAY fire alarm Y Y Provides a manual release with a 10-second delay through a monitor module(connected to a UL-listed pull station) for a releasing zoneSECOND SHOT fire alarm Y Y Provides a second manual release through a monitor module (connected to a UL-listed pull station) for a releasing zonewww.PDF-Zoo.com