Releasing Applications Abort Switches88 NFS-3030 Programming Manual P/N 51345:C 11/4/03Each Cross Zone option and the conditions required to activate releasing zone ZR01 are shown inthe table below, according to the example in Appendix Figure B-9.Using Type Codes for Releasing ZonesThe control panel provides a set of Type Codes designed for releasing applications for inputs andoutputs. This section details how to program each of these Type Codes.Note: Panel circuit modules are not suitable for the release of agents.Type Codes designed for releasing zone inputs (SLC monitor modules).Type Codes designed for releasing zone outputs (SLC control modules).Cross ZoneSelection (Cross=) Condition(s) Required to Activate the Releasing zoneCross=No An alarm from any initiating device activates the releasing zone.Cross=Yes An alarm from any two initiating devices activates the releasing zone.Cross=ZoneFor example:An alarm from two initiating devices mapped to different primarygeneral zones, but mapped to the same releasing zone.• An alarm from L02D101 and L02D103• An alarm from L02D102 and L02D104• An alarm from L02D101 and L02D104• An alarm from L02D102 and L02D103The two detectors listed in each set above are each mapped to differentprimary general zones, but both list ZR01 in their zone maps.Cross=Heat Activation of heat detector L02D104 and one smoke detector(L02D101, L02D102, or L02D103).Type Code What the Type Code does Refer toABORT SWITCH(tracking)Provides an abort function througha monitor module (connected to aUL-listed abort station) for areleasing zone."How to Program an AbortSwitch" on page 90MAN. RELEASE(latching)Provides a manual release througha monitor module (connected to aUL-listed pull station) for areleasing zone."How to Program a ManualRelease Switch" on page 91MAN REL DELAY(latching)Provides a manual release with a10-second delay through a monitormodule (connected to a UL-listedpull station) for a releasing zone."How to Program a ManualRelease Delay Switch" on page 92SECOND SHOT(latching)Provides a second manual releasethrough a monitor module(connected to a UL-listed pullstation) for a releasing zone."How to Program a Second ShotSwitch" on page 94Type Code What the Type Code does Refer toREL END BELL Activates an NAC audio or visualdevice when releasing circuits shutoff."How to Program a Release EndBell Circuit" on page 95REL CKT ULC Directs outputs to perform a releasefunction as required by ULC."How to Program a ULC ReleaseCircuit" on page 96www.PDF-Zoo.com