Releasing Applications Abort Switches90 NFS-3030 Programming Manual P/N 51345:C 11/4/03How to Program an Abort SwitchThe following contains information needed to program an Abort Switch for a monitor module.Description A monitor module, connected to a UL-listed abort station (such as the NotifierNBG-12LRA), used to monitor an abort switch for a releasing zone. Multiplemonitor modules can be programmed with the ABORT SWITCH Type Code. Theywill work like multiple conventional abort switches on a conventional zone.Program Select a monitor module for use as an Abort Switch. While programming thismodule (refer to "Module Point" on page 40 for instructions),1. Select the ABORT SWITCH Type Code.2. Enter the number of the desired releasing zone into the module’s zone map.The releasing zone must be fully programmed, with the Abort Switch typecode included (refer to "Releasing Zone" on page 46).Example A programming example of a monitor module programmed as an Abort Switch forReleasing Zone ZR05.Appendix Figure B-10 Monitor Module Configured as an Abort SwitchSYSTEMNORMALSYSTEMACT IVATEDDetectorR05NBG-12LRAstation withAbort SwitchMonitorModuleType CodeABORT SWITCHSLCoutputmoduleSLCoutputmodulewww.PDF-Zoo.com