Abort Switches Releasing ApplicationsNFS-3030 Programming Manual P/N 51345:C 11/4/03 99How to Program a Release Audible CircuitNote: An output with a REL AUDIBLE Type Code requires the following selections: a Releasing Zone; an outputcircuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No Walk Test.The following contains information needed to program a Release Audible circuit for an SLC orPanel Circuit output module .Description An output module programmed to activate an audio or visual device when allreleasing outputs, programmed to the same Releasing Zone, turn on. Multipleoutputs with the REL AUDIBLE Type Code can be mapped to the same ReleasingZone. When the Releasing Zone activates, all outputs with the REL AUDIBLE TypeCode activate at the same time.Program Select a control module or panel circuit module to use as a releasing circuit. Whileprogramming the point (refer to the Point Programming section of this manual forinstructions),1. Select the REL AUDIBLE Type Code,2. Enter the number of the desired Releasing Zone into the module’s zone map.The releasing zone must be fully programmed (refer to "Releasing Zone" onpage 46).Example A programming example of a control module programmed as a Release Audible circuit forReleasing ZoneZR05.Appendix Figure B-18 Output Module Configured as a ReleaseAudible CircuitType CodeREL AUDIBLEType CodeRELEASE CKTType CodeRELEASE CKTType CodeREL AUDIBLEFor example, an output module programmed with the RELAUDIBLE Type Code activates simultaneously with otheroutputs (modules A & B) programmed for ZR05.ZR05MonitorModule Detector Detector DetectorOutputmoduleSLCoutputmoduleASLCoutputmoduleBOutputmodulewww.PDF-Zoo.com