UniPOS Interactive Fire ControlPanel IFS7002Instruction Manual Page 11Revision 2.05 Of 1076.1.3. Access Level 3Accessible for personnel trained and authorized for:− Reconfiguration of specific data – of the protected site or of the fire control panel – savedin the memory;− Maintenance of the fire control panel.This level has two sublevels of access - 3A and 3B.Level 3, sublevel 3A, is accessed through a password entered at Access level 2. At this sublevelthe functions for reconfiguration of specific data for the protected site or the fire control panel areaccessible (see section 13).Level 3, sublevel 3B is accessed when the fire control panel is opened. The following features areaccessible:− Replacing a burnt fuse;− Connecting fire alarm loops and executive devices.6.1.4. Access Level 4Accessible for personnel trained and authorized by the Producer to repair the fire control paneland to modify the software. Special means are required to enter this level.6.2. Indications and buttons for controlTable 1 gives detail description of the indications for each status, Table 2 presents the basicmeans for control. Appendix 1 shows the front panel of IFS7002.Table 1Conditions of the fire control panel IndicationAll conditions -The fire control panel is power suppliedIndicator Power supply –continuous green lightFire condition Common indicator Fire condition –flashing red lightFault condition -All faults except for Battery LowCommon indicator Fault condition– flashing yellow lightFault condition – System error Indicator System error - continuousyellow lightFault condition -Fault in mains supplyIndicator Fault in mains supply -flashing yellow lightDisabled component -Disabled zone, addressable device or monitoredoutputIndicator Disabled component -continuous yellow lightTest condition Indicator Test –continuous yellow lightFire condition Local sounder – discontinuous signal: 0.5 ssound, followed by 0.5s breakFault condition - All faults except for Battery Low Local sounder – discontinuous signal: 1 ssound, followed by 1 s breakFault condition -Low batteryLocal sounder – discontinuous signal: 1 ssound, followed by 3 s break