UniPOS Interactive Fire ControlPanel IFS7002Instruction Manual Page 93Revision 2.05 Of 10717.5. Power supply connectionTake out the fuse from the terminal with mains fuse (Appendix 3).Connect a feeding cable to the terminal with mains fuse, observing the following positions(Appendix 3):− P – power wire “Phase”;− N – power wire “Null”;− : - safety ground wire.The cable shall be double insulated and of 0,5mm2 section for the power supply wires, and of1,5mm2 section for the safety ground wire.The other end of the feeding cable is connected to the mains power supply by means of junctionbox.The mains power supply of the fire control panel shall be in a separate loop.18. Fire control panel start upMake sure that the connection to mains power supply is properly made.Make sure that the periphery devices are correctly connected.Place the fuse in the terminal with mains fuse, the display illuminates and appears the textSystem operations.Connect the feeding cable and the backup batteries; the batteries shall be in a series connection.Connect the red wire to the positive backup battery pole, and the blue wire - to the negative pole.The overall voltage of both batteries shall not exceed 17.6V, otherwise the fire control panel will notrecognize them.Enter SetUp Mode and configure the control panel as follows:1. Save the default parameters (except for a control panel with factory set up parameters) –Function Default parameters (see section 13.10);2. Select a language for the messages – Menu Panel configuration (see section 13.2);3. Set the loop parameters – Menu Loop parameters (see section 13.4.1):♦ Loop status – On or Off;♦ Maximum current in the loop;4. Exclude all unused devices in the loops, if any – Menu Exclude devices (see section 13.7.4);5. Start clean initialization of the addressable devices in the loops – Function Clean initialization(see section 13.7.2);6. Run a check on the initialization of the addressable devices in the loops – Menu Check (seesection 13.7.5);7. If the configuration of any of the loops does not cover your requirements, rearrange theaddressable devices and repeat operations 4 – 6 set herein (regarding section 4, be advisedthat you might need to include devices);8. Entera text message for each addressable device in the loop – Menu Device parameters(see section 13.4.2);9. Form fire alarm zones and set their parameters up – Menu Zones (see section 13.5):♦ Devices in the zone – Menu Devices (see section 13.5.1);♦ Аoutputs associated to the zone – Menus Fire Phase 1 Outputs and Fire Phase 2Outputs (see section 13.5.2);♦ Zone parameters: Manual call point priority, Coincidence mode, Time Fire Phase 1 –Phase 2 and Inspection Time – Menu Zone parameters (see section 13.5.3);♦ Тtext message for the zone – Screen Text message (see section 13.5.4);10. Set up parameters of any addressable inputs – Menu Inputs (see section 13.6);11. Activate the power loop if necessary – Menu Panel configuration (see section 13.2);12. Enter the passwords for Access Level 2 and Access Level 3 – Menu New passwords (seesection 13.9);13. Clear the archive – Function Clear archive (see section 13.11).Upon exit of SetUp Mode the control panel runs again System operations and enters Duty Mode– the fire controlpanel is ready to provide site protection.19. TroubleshootingPossible problems and methods of troubleshooting are described in Table 4.