UniPOS Interactive Fire ControlPanel IFS7002Instruction Manual Page 55Revision 2.05 Of 107The menu has the followinglayout:The information for the firstactive parameter is displayed ininversive colours (white letters onblack background). Buttons andat the right panel side allow theuser to move between the activeparameters only.To edit the parameters usebutton – each time you press itthe parameter value changes to thenext acceptable value.13.3. Menu Panel parametersUse the menu when the control panel is integrated into a local network of panels (see InteractiveFire Control Panel IFS7002 – Operation in Local Network).13.4. Menu LoopsThe menu is provided for set up of fire alarm loops and devices integrated in the loops. It containstwo submenus of identical layout – for Loop 1 and for Loop 2. Each submenu contains:− Menu Loop parameters;− Menu Device parameters.13.4.1. Menu Loop parametersThe menu allows the user toadjust the parameters of the firealarm loop:− Loop status - On or Off− Maximum current value of theloop;− Number of devices integratedin the loop.To edit the Status parameter usebutton – press the button toalternatively change the parameterfrom On to Off and vice versa.Use the digit buttons to edit theparameters Maximum current andNumber of devices. When you pressbutton the digit at the cursor’sleft side is deleted.If the values of Maximum current and Number of devices are out of the specified limits they willnot be accepted and saved when you press button and the reminder Data not saved willremain active.СMode: DAY 14:18:38 Tue 22 Mar 2005Set Up Loop 1Status: OnMax current (1 – 120 mA): 120 mANumber of Devices (0 – 125): 370 1 2 3 4 5 6 7 8 9 СMode: DAY 12:51:18 Tue 22 Mar 2005Panel configurationLocal Network: nonePeriphery Module 1: nonePeriphery Module 2: nonePeriphery Module 3: nonePower loop: OnLanguage: English