UniPOS Interactive Fire ControlPanel IFS7002Instruction Manual Page 20Revision 2.05 Of 1078.3.7. Button (Exit)When Fire condition is in combination with Information and Control Mode, press the button andthe fire control panel exits Information and Control Mode and on the display appear all three panels ofthe screen for Fire condition.9. Fault Condition9.1. DescriptionThe fire control panel enters Fault Condition when any of the events below have been registered:− Fatal system error;− Battery low – backup batteries discharged due to interruption of mains supply;− Fault in a processor programme;− Fault in a module;− Fault in the real time clock;− Fault in the external memory;− Fault in a loop – a short circuit or a break;− Loop not initialized;− Higher number of devices in the fire alarm loop;− Fault in a zone – upon detection of fault condition in a device, integrated in the zone;− Removed device;− Fault condition in a device;− Activated isolator of a device;− Activated isolator at the Power loop of a device;− Contaminated fire detector (for optical detectors|;− Communication error− Device not initialized (detected new device in a loop);− Exchanged devices;− Different identification number of a device,− Different device type;− Different device class;− Fault in a monitored output – short circuit or break;− Fault in the mains supply;− Fault in the backup batteries supply;− Short circuited ground wire;− Fault in the positive supply of the loops;− Fault in the negative supply of the loops;− Fault in external devices supply.Where a fatal system error occurs, the main processor can not continue operation and the firecontrol panel does not control loops, outputs and other periphery devices. To exit fatal system erroryou have to cut off the mains supply and to repair the control panel.Battery Low is a fatal non-system error; zones and outputs are not being services. The fire controlpanel enters a special condition:− A discontinuous sound signal is produced - 1s sound, 3s break for at least 1 hour;− Only the green LED indicator is illuminated (Power supply).− The lighting of the display is extinguished;− Only the supply voltages are controlled.The condition is exited automatically 20 s after the mains supply is restored.All other fault conditions are not fatal and switch off some periphery devices. The condition isexited automatically 20 s after the fault is suspended.Upon fault condition Short circuit to ground wire where an element of a monitored output is shortcircuited, fault condition in the monitored output (break) is also developed.Fault condition is indicated by LEDs indicators and a text message on the LCD display.