UniPOS Interactive Fire ControlPanel IFS7002Instruction Manual Page 9Revision 2.05 Of 1074.5. Monitored outputs− Type - potential− Еlectrical characteristics - (24±5)V/100mA4.6. Relay outputs for fire conditions− Type - potential free, switching,− Electrical characteristics - 3A/125VAC; 3A/30VDC4.7. Relay output for fault conditions− Type - potential free, switching− Electrical characteristics - 3A/125VAC; 3A/30VDC4.8. Performance− Control over fire alarm loops and monitored outputs for fault conditions (short circuitand interruption) and automatic reset− Detection of removed devices in the loops and automatic reset− Ability to set the zones in Coincidence Mode− Two phases of Fire condition, programmable time for Fire condition stage I,separately for each zone− Option to prolong the time period for Fire condition stage I with programmableinspection period, specified for each zone− Built-in sounder for fire condition – one tonal, discontinuous, can be switched off− Built-in sounder for fault condition – one tonal, discontinuous, can be switched off− Built-in real time clock− Set of test modes and options for adjustment:♦ Setting the clock;♦ Check ups on light and sound indications;♦ Test of fire alarm zones;♦ Adjustment of outputs and integrated external devices;♦ Programming of parameters and modes of operation;♦ Remote programming of the parameters from distant operator control point;− Energy independent archive of registered events with the events type, date and hour– up to 1023 events;− Interfaces for communication with external devices - CAN 2.0B and RS-232(directly or via modem).4.9. Indications of registered events− Light indication - LED− Text messages - LCD display,320 х 240 points, backlit− Sound signaling - built-in sounder4.10. Power supply4.10.1. Mains− voltage - 220/230V− frequency - 50Hz4.10.2. Back up batteries− battery type - lead, gel electrolyte− number of batteries - 2 pcs− connection - serial connection− nominal voltage of the back up battery - 24V− nominal capacity C 20 - 18Ah− extreme discharge voltage - 21V− charge voltage - 28,2V4.10.3. Consumption on back up batteries supply− at 24V - < 250mA− at 26V - < 240mA