UniPOS Interactive Fire ControlPanel IFS7002Instruction Manual Page 15Revision 2.05 Of 107Depending on the result of the verification, the fire control panel would execute the followingoperations:a) if the fire control panel is able to synonymously detect the location of a device in a loop and toverify its parameters against these saved in the energy independent memory:♦ the device is placed in service with its previous address in the loop;♦ the fault Removed device is cleared;b) if the fire control panel is able to synonymously detect the location of a device in a loop, butthe device’s parameters do not conform with these saved in the energy independent memory:♦ the device is placed in service with an address, corresponding to device’s location inthe loop;♦ a fault condition due to incompliance with identification number, type or class isadded;♦ the device is included in the Service zone;c) if the fire control panel is not able to synonymously detect the location of a device in a loop(two or more serial devices forming an area are removed, but only some replaced):♦ the device is placed in service with the first available address from the correspondingarea in the loop;♦ a fault is added, Device not initialized;♦ the device is included in the Service zone.When the last device for Removed devices area is placed, the fire control panel willsynonymously detect their location. For the last placed device the fire control panel will run operationsa) or b). For previously placed devices the fire control panel will run the following operations:d) if the fire control panel detects compliance of parameters with these saved in the energyindependent memory:♦ the device is placed in service with its previous address in the loop;♦ the faults Removed device and Device not initialized are cleared;♦ the device is excluded from the Service zone;e) if the fire control panel detects incompliance of parameters with these saved in the energyindependent memory:♦ the device is placed in service with an address, corresponding to device’s location inthe loop;♦ a fault condition due to incompliance with identification number, type or class isadded;♦ the device remains in the Service zone.In cases b), c) and e) the following actions can be taken:− if any devices seemed to be involuntarily exchanged, they shall be placed on the properlocations;− the device can be excluded from the Service zone by using the Menu Readdressing (seesection 13.7.3) and setting the proper address;− to save the new loop configuration by using the Function Clean initialization (seesection 13.7.2).When a new addressable device (exceeding the number of addressable devices in the loop), thefire control panel sets a temporary address for this device (the text message Reinitialization appearson the lower end of the display) but ignores the device during further operation. To include the devicein the loop configuration you need to start the Function Clean initialization (see section 13.7.2).7. Duty Mode7.1. DescriptionThe fire control panel is in Duty Mode, when it is not in any other of the rest 7 possible conditions.7.2. Indication7.2.1. LED and sound indicationIn Duty Mode the green LED indicator is activated (Power supply). The local sounder is off.