4.6 Data Transfer without Using the MPE7204.6.1 Using USB Memory4-734 Creating User Programs Batch Saving to USB Memory1. Turn ON the power supply to the CPU Unit/CPU Module.2. Make sure the security password has not been set for the CPU Unit/CPU Module. Oth-erwise, any attempts to perform a batch save will fail. Refer to the following section fordetails on removing the security password.Deleting a Password (page 6-8)3. Insert the USB memory device that contains the application data to transfer into theUSB connector on the CPU Unit/CPU Module.4. Set the INIT pin on the mode switch 1 on the CPU Unit/CPU Module according to theregister type to save.5. Press and hold the STOP/SAVE switch on the CPU Unit/CPU Module for at least twoseconds. The batch save operation starts.When a save operation is performed to the USB memory device, any data that is stored on theUSB memory device will be overwritten.Registers toSaveINIT Switch SettingOFF ONM registers Transferred. Not transferred.G registers Transferred. Not transferred.S registers Transferred. Not transferred.I registers Transferred. Not transferred.O registers Transferred. Not transferred.C registersAlways transferred regardless of DIP switch setting.# registersD registersIf the save operation fails, an error code will be displayed on the CPU Unit/CPU Module.Refer to the following manual to troubleshoot the problem, then perform the batch saveagain.MP3000 Series MP3200/MP3300 Troubleshooting Manual (Manual No.: SIEP C880725 01)NoteInformation