4.3 The Drive and Programming ModesYASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual 103Start-Up Programming &Operation4The example below is continued from page 102. Here, parameter C1-01 is accessed usingthe Verify Menu and is changed again to 20.0 s.To check the list of edited parameters:◆ Switching Between LOCAL and REMOTEEntering the run command using the LED operator is referred to as LOCAL, while enteringthe run command from an external device via the control circuit terminals or network optioncard is referred to as Remote.WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is alreadyapplied when switching from LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or seriousinjury. Be sure all personnel are clear of rotating machinery and electrical connections prior to switchingbetween LOCAL mode and REMOTE mode.There are three ways to switch between LOCAL and REMOTE.Note: 1. After selecting LOCAL, LO/RE will remain lit.2. The drive will not allow the user to switch between LOCAL and REMOTE during run.■ Using the LO/RE Key on the LED OperatorStep Display/Result1. Turn on the power to the drive. The initial display appears. ⇒2. Press until the display reads, “Verify.” ⇒3.Press to enter the list of parameters that have been editedfrom their original default settings.Scroll through the list by pressing the key.⇒4. Press the key until C1-01 appears. ⇒5. Press the key to access the setting value.(number farthestto the left flashes)⇒Step Display/Result1. Turn on the power to the drive. The initial display appears. ⇒