B.2 Parameter TableYASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual 333Parameter ListB◆ F: OptionsF parameters are used to program the drive for PG feedback and to function with optioncards.<52> Parameter ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output FrequencyVoltage 2, are set to 0.<53> Default setting depends on the control mode for motor 2 set in parameter E3-01. The given value is for V/fcontrol.<57> Default setting value is dependent on parameter o2-04, Drive/kVA Selection and C6-01, Drive Duty Selection..No. Name Description Range Def.ControlModeAddr.Hex Pg.V/fOLVPMF1: Simple PG V/f ParametersUse F1 parameters to set up the drive for Simple PG V/f control. These parameters are enabled only when H6-01 = 03F1-02Operation Selection atPG Open Circuit(PGO)Sets stopping method when a PG open circuitfault (PGO) occurs. Refer to parameter F1-14.0: Ramp to Stop - Decelerate to stop using theactive deceleration time.1: Coast to Stop2: Fast-stop - Decelerate to stop using thedeceleration time in C1-09.3: Alarm only - Drive continues operation.0 to 3 1 A − − 381 —F1-03 Operation Selection atOverspeed (OS)Sets the stopping method when an overspeed(OS) fault occurs. Refer to F1-08 and F1-09.0: Ramp to stop - Decelerate to stop using theactive deceleration time.1: Coast to stop2: Fast - Stop - Decelerate to stop using thedeceleration time in C1-09.3: Alarm Only - Drive continues operation.0 to 3 1 A − − 382 —F1-04 Operation Selection atDeviationSets the stopping method when a speeddeviation (DEV) fault occurs. Refer to F1-10and F1-11.0: Ramp to stop - Decelerate to stop using theactive deceleration time.1: Coast to stop2: Fast-stop - Decelerate to stop using thedeceleration time in C1-09.3: Alarm only - Drive continues operation.0 to 3 3 A − − 383 —F1-08 Overspeed DetectionLevelSets the speed feedback level which has to beexceeded for the time set in F1-09 before anOS fault will occur.Set as a percentage of the maximum outputfrequency (E1-04).0 to 120 115% A − − 387 —