B.2 Parameter TableYASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual 337Parameter ListB◆ H Parameters: Multi-Function TerminalsH parameters assign functions to the multi-function input and output terminals.No. Name Description Range Def.ControlModeAddr.HexPg.V/fOLVPMH1: Multi-Function Digital InputH1 parameters to assign functions to the multi-function digital input terminals. Unused terminals should be set to "F".H1-01 Multi-Function Digital Input TerminalS1 Function SelectionSelects the function ofterminals S1 to S7Refer to “Multi-FunctionDigital Input SelectionTable” for a description ofsetting values.1 to 9F<40>40 A A A 438 —H1-02 Multi-Function Digital Input TerminalS2 Function Selection 41 A A A 439 —H1-03 Multi-Function Digital Input TerminalS3 Function Selection 24 A A A 400 —H1-04 Multi-Function Digital Input TerminalS4 Function Selection 14 A A A 401 —H1-05 Multi-Function Digital Input TerminalS5 Function Selection3(0)<18><18> Parenthetical value is the default when parameter A1-03 = 3330 3-Wire Initialization.<40> The availability of certain functions depends on the control method used.A A A 402 —H1-06 Multi-Function Digital Input TerminalS6 Function Selection4(3)<18> A A A 403 —H1-07 Multi-Function Digital Input TerminalS7 Function Selection6(4)<18> A A A 404 —H1 Multi-Function Digital Input SelectionsH1-
Setting Function DescriptionControlMode Pg.V/fOLVPM0 3-Wire Sequence Closed: Reverse rotation (only if the drive is set up for 3-wire sequence) O O O —1 Local/Remote Selection Open: Remote, Reference 1 or 2 (b1-01/02 or b1-15/16)Closed: Local, LED operator is run and reference source O O O —2 External Reference 1/2 Open: Run and frequency reference source 1 (b1-01/02)Closed: Run and frequency reference source 2 (b1-15/16) O O O —