D.2 European StandardsYASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual 415Standards ComplianceD■ Guarding Against Harmful MaterialsWhen installing IP20/Open-Chassis drives, use an enclosure that prevents foreign materialfrom entering the drive from above or below.■ GroundingThe drive is designed to be used in T-N (grounded neutral point) networks. If installing thedrive in other types of grounded systems, contact your dealer or Yaskawa for instructions.◆ EMC Guidelines ComplianceThis drive is tested according to European standards EN61800-3 and it complies with theEMC guidelines.■ EMC Filter InstallationThe following conditions must be met to ensure continued compliance with guidelines.• EMC Filter Selection: Refer to Yaskawa catalog for EMC filter selection.• EMC Filter Installation: Refer to option manual for option installation instructions.Installation MethodVerify the following installation conditions to ensure that other devices and machinery usedin combination with this drive also comply with EMC guidelines.1. Install an EMC noise filter to the input side specified by Yaskawa for compliancewith European standards.2. Place the drive and EMC noise filter in the same enclosure.3. Use braided shield cable for the drive and motor wiring or run the wiring through ametal conduit.4. Keep wiring as short as possible. Ground the shield on both the drive side and themotor side.4A0018Not Available50 A6T504A0023 60 A6T604A0031 70 A6T704A0038 80 A6T80Drive Model CIMR-V
Time Delay/Class RK5 Fuses600 Vac, 200 kAIRFuse Ampere RatingNon-Time Delay/Class T Fuses600 Vac, 200 kAIR