YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual 307B.2 Parameter TableParameter ListBB.2 Parameter Table◆ A: Initialization ParametersThe A parameter group creates the operating environment for the drive. This includes theparameter Access Level, Motor Control Method, Password, User Parameters and more.No. Name Description Range Def.ControlModeAddr.HexPg.V/fOLVPMA1: Initialization ParametersUse A1 parameters to configure the basic environment for drive operation.A1-01<22><16>Access LevelSelectionSelects which parameters are accessible via thedigital operator.0: Operation only1: User Parameters (access to a set of parametersselected by the user)2: Advanced Access Level0 to 2 2 A A A 101H —A1-02 Control MethodSelectionSelects the Control Method of the drive.0: V/f Control without PG2: Open Loop Vector (OLV)5: PM Open Loop Vector (PM)Note: Does notreturn to the default setting when the drive isinitialized.0, 2, 5 0 S S S 102 122A1-03 InitializeParametersResets all parameters to factory default settings.(Initializes the drive then returns A1-03 to 0)0: No Initialize1110: User Initialize (First set user parametervalues must be stored using parameter o2-03)2220: 2-Wire Initialization3330: 3-Wire Initialization5550: OPE04 Error Reset0 to3330 0 A A A 103 —The following parameters are notreset when the performinginitialization:A1-00, A1-02, A1-07, and all U2and U3 monitors.A1-04 Password 1When the value set into A1-04 does not match thevalue set into A1-05, parameters A1-01 thru A1-03, A1-06, and A2-01 thru A2-32 cannot bechanged.0 to9999 0 A A A 104 —A1-05 Password 20 to9999 0 A A A 105 —This parameter is hidden fromview. To access A1-05, firstdisplay A1-04. Then press theSTOP key while holding downthe up arrow key. ParameterA1-05 will appear.—