B.2 Parameter Table308 YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual◆ b: ApplicationApplication parameters configure the Run Command Source, DC Injection Braking, SpeedSearch, Timer functions, PID control, the Dwell function, Energy Savings and a variety ofother application-related settings.A1-06 ApplicationPresetSets parameters that are commonly used in certainapplications to A2-01 through A2-16 for easieraccess.0: General-purpose (A2 parameters are notaffected)1: Water supply pump2: Conveyor3: Exhaust fan4: HVAC fan5: Air compressor6: Crane (Hoist)7: Crane (Travelling)0 to 7 0 A A A 127 —A1-07DriveWorksEZFunctionSelection0: Disabled1: Enabled2: Multi-function input (enabled when H1-
=9F)0 to 2 0 A A A —A2: User ParametersUse A2 parameters to program the drive.A2-01toA2-32User Parameters,1 to 32Parameters that were recently edited are listed here.The user can also select parameters to appear herefor quick access.Parameters will be stored here for quick accesswhen A1-01 = 1.b1-01 too2-08--<16> A A A 106 to125 —A2-33User ParameterAutomaticSelection0: Parameters A2-01 through A2-32 are reservedfor the user to create a list of User Parameters.1: Save history of recently viewed parameters.Recently edited parameters will be saved to A2-17through A2-32 for quick access.0,1 1<4> A A A 126 —<4> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06does not = 0.<16> Default setting value is dependent on parameter A1-06, Application Selection.<22> Parameter can be changed during run.No. Name Description Range Def.ControlModeAddr.HexPg.V/fOLVPM