7.4 Installing Peripheral DevicesYASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual 277Peripheral Devices &Options7◆ EMC Filter InstallationThis drive is tested according to European standards EN61800-3 and it complies with theEMC guidelines. The following conditions must be met to ensure continued compliancewith guidelines.• EMC Filter Selection: Refer to Yaskawa catalog for EMC filter selection and partnumbers.• EMC Filter Installation: Refer to option manual for option installation instructions.■ Installation MethodVerify the following installation conditions to ensure that other devices and machinery usedin combination with this drive also comply with EMC guidelines.1. Install an EMC noise filter to the input side specified by Yaskawa for compliancewith European standards.2. Place the drive and EMC noise filter in the same enclosure.3. Use braided shield cable for the drive and motor wiring or run the wiring through ametal conduit.4. Keep wiring as short as possible. Ground the shield on both the drive side and themotor side (Figure 7.11).Figure 7.11Figure 7.11 Installation Method5. Ground the largest possible surface area of the shield to the metal conduit whenusing braided shield cable. Yaskawa recommends using a cable clamp(Figure 7.12).A – Drive D – Metal conduitB – 20 m max cable length betweendrive and motorE – Ground wire should be as short aspossible.C – MotorABDECMU/T1V/T2W/T3UVW