4.7 Test Run166 YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual◆ Jog Operation: FJOG/RJOGDigital inputs programmed as Forward Jog (H1-
= 12) and Reverse Jog (H1-
= 13)will be Jog inputs that do not require a run command. Closing the terminal set for ForwardJog input will cause the drive to ramp to the Jog Frequency Reference (d1-17) in the forwarddirection. The Reverse Jog will cause the same action in the reverse direction. The ForwardJog and Reverse Jog can be set independently.■ Jog Operation Parameters■ Selections for Digital Input Terminals S1 to S7 (H1-01 to H1-07)■ Connection Example for the Jog FunctionIn this example, H1-07 = 12 and d1-17 = 6.0 Hz.Figure 4.30Figure 4.30 Jog Command from External TerminalsNo. Name Description SettingRangeDefaultSettingd1-17 Jog FrequencyReferenceFrequency reference when: “Jog Frequency Reference” isselected via multi-function input terminals. “Jog FrequencyReference” has priority over “Multi-Step Speed Reference 1 to16." Parameter d1-17 is also the reference for the JOG key onthe digital operator, and the multi-function inputs “ForwardJog” and “Reverse Jog.”0.00 to400.00 6.00 HzSetting Name12 FJOG Command (ON: rotates forward at the Jog frequency set to d1-17)13 RJOG Command (ON: rotates in reverse at the Jog frequency set to d1-17)R/L1S/L2T/L3U/T1V/T2W/T3MThree-Phase 200 Vac(400 Vac)S7 (FJ0G)SCDrive