4.6 Basic Drive Setup Adjustments146 YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up ManualAdjusting the Analog Output Terminal Voltage with H4-02 and H4-03Note: This example continues from Step 3 in the previous example.Figure 4.26Figure 4.26 Adjusting the Monitor Output◆ Motor Protection: L1-01 and L1-02This section explains how to set motor overload protection.■ Electronic Thermal Motor ProtectionThe drive has built-in electronic thermal overload protection to detect overload conditions.This protection meets standards set by UL and cUL for motor thermal overload protection.The protective feature is activated when the output current rises above the motor ratedcurrent for a specified time. This speed sensitive protective feature interrupts the motorcurrent to protect the motor wiring and windings in the event of overload, eliminating theneed for an external overload device. When multiple motors are used with a single drive,separate overload devices are required to properly protect the individual motor branches.9. Press the key until back at the Top Screen. ⇒Step Display/Result1. Select H4-02 or H4-03 by pressing the and keys. ⇒2.Press the key while the drive is stopped and the followingvoltage is output for adjustment: output voltage = (10 V x OutputGain (H4-02) + Output Bias (H4-03). Using this output, adjustoutput gain (H4-02) and output bias (H4-03).⇒Step Display/ResultOutput Voltage10Gain V10 V100%0%0 V MonitorContents100(%)10Bias V100(%)