Application macros 141 Default parameter settings for the PID control macroBelow is a listing of default parameter values that differ from those listed for theFactory macro in Parameter listing (page 156).Note: The macro selection does not affect parameter group 41 Process PID set 2.Parameter PID control macro defaultNo. Name12.27 AI2 min 4.00019.11 Ext1/Ext2 selection DI320.01 Ext1 commands In1 Start20.04 Ext1 in2 source Not selected20.06 Ext2 commands In1 Start20.08 Ext2 in1 source DI620.12 Run enable 1 source DI522.12 Speed ref2 source PID22.22 Constant speed sel1 DI423.11 Ramp set selection Acc/Dec time 131.11 Fault reset selection Not selected40.07 Set 1 PID operation mode On when drive running40.08 Set 1 feedback 1 source AI2 scaled40.11 Set 1 feedback filter time 0.040 s40.35 Set 1 derivation filter time 1.0 s40.60 Set 1 PID activation source Follow Ext1/Ext2 selection