Parameters 36545.18 CO2 conversionfactorDefines a factor for conversion of saved energy into CO 2emissions (kg/kWh or tn/MWh).0.500tn/MWh0.000 … 65.535tn/MWhFactor for conversion of saved energy into CO2 emissions. 1 = 1 tn/MWh45.19 Comparison power Actual power that the motor absorbs when connected direct-on-line and operating the application. The value is used forreference when energy savings are calculated.Note: The accuracy of the energy savings calculation isdirectly dependent on the accuracy of this value. If nothing isentered here, then the nominal motor power is used by thecalculation, but that may inflate the energy savings reportedas many motors do not absorb nameplate power.0.0 kW0.0 … 100000.0 kW Motor power. See par.46.04.45.21 Energy calculationsresetResets the savings counter parameters 45.01…45.09. DoneDone Reset not requested (normal operation), or reset complete. 0Reset Reset the savings counter parameters. The value revertsautomatically to Done.14646 Monitoring/scalingsettingsSpeed supervision settings; actual signal filtering; generalscaling settings.46.01 Speed scaling Defines the maximum speed value used to define theacceleration ramp rate and the initial speed value used todefine the deceleration ramp rate (see parameter group 23Speed reference ramp). The speed acceleration anddeceleration ramp times are therefore related to this value(not to parameter 30.12 Maximum speed).Also defines the 16-bit scaling of speed-related parameters.The value of this parameter corresponds to 20000 infieldbus, master/follower etc. communication.1500.00 rpm;1800.00 rpm(95.20 b0)0.10 … 30000.00rpmAcceleration/deceleration terminal/initial speed. 1 = 1 rpm46.02 Frequency scaling Defines the maximum frequency value used to define theacceleration ramp rate and the initial frequency value usedto define deceleration ramp rate (see parameter group 28Frequency reference chain). The frequency accelerationand deceleration ramp times are therefore related to thisvalue (not to parameter 30.14 Maximum frequency).Also defines the 16-bit scaling of frequency-relatedparameters. The value of this parameter corresponds to20000 in fieldbus, master/follower etc. communication.50.00 Hz;60.00 Hz(95.20 b0)0.10 … 1000.00 Hz Acceleration/deceleration terminal/initial frequency. 10 = 1 Hz46.03 Torque scaling Defines the 16-bit scaling of torque parameters. The value ofthis parameter (in percent of nominal motor torque)corresponds to 10000 in fieldbus, master/follower etc.communication.100.0%0.1 … 1000.0% Torque corresponding to 10000 on fieldbus. 10 = 1%No. Name/Value Description Def/FbEq16