222 Parameters14.91 AO2 source max (Visible when 14.01 Module 1 type = FAIO-01)Defines the real value of the signal (selected by parameter14.87 AO2 source) that corresponds to the maximum AO2output value (defined by parameter 14.93 AO2 out at AO2src max). See parameter 14.90 AO2 source min.100.0-32768.0 …32767.0Real signal value corresponding to maximum AO2 outputvalue.1 = 114.92 AO2 out at AO2 srcmin(Visible when 14.01 Module 1 type = FAIO-01)Defines the minimum output value for analog output AO2.See also drawing at parameter 14.90 AO2 source min.0.000 mA0.000 … 22.000 mA Minimum AO2 output value. 1000 = 1 mA14.93 AO2 out at AO2 srcmax(Visible when 14.01 Module 1 type = FAIO-01)Defines the maximum output value for analog output AO2.See also drawing at parameter 14.90 AO2 source min.10.000 mA0.000 … 22.000 mA Maximum AO2 output value. 1000 = 1 mA1515 I/O extension module2Configuration of I/O extension module 2.See also section Programmable I/O extensions (page 72).Note: The contents of the parameter group vary accordingto the selected I/O extension module type.15.01 Module 2 type See parameter 14.01 Module 1 type. None15.02 Module 2 location See parameter 14.02 Module 1 location. Slot 115.03 Module 2 status See parameter 14.03 Module 1 status. No option15.05 DI status (Visible when 15.01 Module 2 type = FDIO-01)See parameter 14.05 DI status.-15.05 DIO status (Visible when 15.01 Module 2 type = FIO-01 or FIO-11)See parameter 14.05 DIO status.-15.06 DI delayed status (Visible when 15.01 Module 2 type = FDIO-01)See parameter 14.06 DI delayed status.-15.06 DIO delayed status (Visible when 15.01 Module 2 type = FIO-01 or FIO-11)See parameter 14.06 DIO delayed status.-15.08 DI filter time (Visible when 15.01 Module 2 type = FDIO-01)See parameter 14.08 DI filter time.10.0 ms15.08 DIO filter time (Visible when 15.01 Module 2 type = FIO-01 or FIO-11)See parameter 14.08 DIO filter time.10.0 ms15.09 DIO1 function (Visible when 15.01 Module 2 type = FIO-01 or FIO-11)See parameter 14.09 DIO1 function.Input15.11 DIO1 output source (Visible when 15.01 Module 2 type = FIO-01 or FIO-11)See parameter 14.11 DIO1 output source.Notenergized15.12 DI1 ON delay (Visible when 15.01 Module 2 type = FDIO-01)See parameter 14.12 DI1 ON delay.0.00 s15.12 DIO1 ON delay (Visible when 15.01 Module 2 type = FIO-01 or FIO-11)See parameter 14.12 DIO1 ON delay.0.00 s15.13 DI1 OFF delay (Visible when 15.01 Module 2 type = FDIO-01)See parameter 14.13 DI1 OFF delay.0.00 s15.13 DIO1 OFF delay (Visible when 15.01 Module 2 type = FIO-01 or FIO-11)See parameter 14.13 DIO1 OFF delay.0.00 sNo. Name/Value Description Def/FbEq16