Parameters 3233535 Motor thermalprotectionMotor thermal protection settings such as temperaturemeasurement configuration, load curve definition and motorfan control configuration.See also section Motor thermal protection (page 120).35.01 Motor estimatedtemperatureDisplays the motor temperature as estimated by the internalmotor thermal protection model (see parameters35.50…35.55). The unit is selected by parameter 96.16 UnitselectionThis parameter is read-only.--60 … 1000 °C or °F Estimated motor temperature. 1 = 1°35.02 Measuredtemperature 1Displays the temperature received through the sourcedefined by parameter 35.11 Temperature 1 source. The unitis selected by parameter 96.16 Unit selection.Note: With a PTC sensor, the unit is ohms.This parameter is read-only.--60 … 1000 °C,-76…1832 °F,0 ohm or[35.12] ohmMeasured temperature 1. 1 = 1 unit35.03 Measuredtemperature 2Displays the temperature received through the sourcedefined by parameter 35.21 Temperature 2 source. The unitis selected by parameter 96.16 Unit selection.Note: With a PTC sensor, the unit is ohms.This parameter is read-only.--60 … 1000 °C,-76…1832 °F,0 ohm or[35.22] ohmMeasured temperature 2. 1 = 1 unit35.04 FPTC status word Displays the status of optional FPTC-xx thermistorprotection modules. The word can be used as the source ofe.g. external events.Note: The “module found” bits are updated regardless ofwhether the corresponding module is activated. However,the “fault active” and “warning active” bits are not updated ifthe module is not activated. Modules are activated byparameter 35.30 FPTC configuration word.This parameter is read-only.-0000h…FFFFh FPTC-xx status word. 1 = 1No. Name/Value Description Def/FbEq16Bit Name Description0 Module found in slot 1 1 = Yes: An FPTC-xx module has been detected in slot 1.1 Fault active in slot 1 1 = Yes: The module in slot 1 has an active fault.2 Warning active in slot 1 1 = Yes: The module in slot 1 has an active warning.3 Module found in slot 2 1 = Yes: An FPTC-xx module has been detected in slot 2.4 Fault active in slot 2 1 = Yes: The module in slot 2 has an active fault.5 Warning active in slot 2 1 = Yes: The module in slot 2 has an active warning.6 Module found in slot 3 1 = Yes: An FPTC-xx module has been detected in slot 3.7 Fault active in slot 3 1 = Yes: The module in slot 3 has an active fault.8 Warning active in slot 3 1 = Yes: The module in slot 3 has an active warning.9…15 Reserved