20 Start-up guide for ACS880 winder control programDrive start-up Before you startMake sure that the drive has been mechanically and electrically installed asdescribed in the appropriate Quick installation guide and/or Hardware manual. SafetyWARNING! All electrical installation and maintenance work on the drive shouldbe carried out by qualified electricians only.Never work on the drive, the braking copper circuit, the motor cable or the motorwhen power is applied to the drive. Always ensure by measuring that no voltage isactually present. Start-upSafetyWARNING! Obey all safety instructions for the drive. Only qualified electricians areallowed to start up the drive.Check the installation. See the installation checklist in the appropriate Hardware manual.Check that the starting of the motor does not cause any danger.De-couple the driven machine if• there is a risk of damage in case of an incorrect direction of rotation, or• a Normal ID run is required during the drive start-up, when the load torque is higherthan 20% or the machinery is not able to withstand the nominal torque transient duringthe ID run.1 – Power-up, date and time settingsPower up the drive.Note: It is normal that warning messagesappear at various points along the start-upprocess. To hide a message and to resumethe start-up process, press .Hide any warnings now to enter the Homeview (shown on the right).The two commands at the bottom of thedisplay (in this case, Options and Menu),show the functions of the two softkeysand located below the display. Thecommands assigned to the softkeys varydepending on the context.Remote 0.0 rpm0.000.00Motor torque %% 0.0Motor currentAMotor speed usedrpmOptions 12:34 Menu