386 ParametersRef2 16bit Reference REF2 (16 bits) 3SW 16bit Status Word (16 bits) 4Act1 16bit Actual value ACT1 (16 bits) 5Act2 16bit Actual value ACT2 (16 bits) 6CW 32bit Control Word (32 bits) 11Ref1 32bit Reference REF1 (32 bits) 12Ref2 32bit Reference REF2 (32 bits) 13SW 32bit Status Word (32 bits) 14Act1 32bit Actual value ACT1 (32 bits) 15Act2 32bit Actual value ACT2 (32 bits) 16SW2 16bit Status Word 2 (16 bits) 24Other Source selection (see Terms and abbreviations onpage 152).-… … … …55.12 FBA B data in12 See parameter 55.01 FBA B data in1. None5656 FBA B data out Selection of data to be transferred from fieldbus controller todrive through fieldbus adapter B.56.01 FBA B data out1 Parameters 56.01…56.12 select data to be transferred fromthe fieldbus controller to the drive through fieldbusadapter B.NoneNone None. 0CW 16bit Control Word (16 bits) 1Ref1 16bit Reference REF1 (16 bits) 2Ref2 16bit Reference REF2 (16 bits) 3CW 32bit Control Word (32 bits) 11Ref1 32bit Reference REF1 (32 bits) 12Ref2 32bit Reference REF2 (32 bits) 13CW2 16bit Control Word 2 (16 bits) 21Other Source selection (see Terms and abbreviations onpage 152).-… … … …56.12 FBA B data out12 See parameter 56.01 FBA B data out1. None5858 Embedded fieldbus Configuration of the embedded fieldbus (EFB) interface.See also chapter Fieldbus control through a fieldbus adapter(page 631).58.01 Protocol enable Enables/disables the embedded fieldbus interface andselects the protocol to use.Note: When the embedded fieldbus interface is enabled, thedrive-to-drive link functionality is automatically disabled.NoneNone None (communication disabled). 0Modbus RTU Embedded fieldbus interface is enabled and uses theModbus RTU protocol.1No. Name/Value Description Def/FbEq16