382 Parameters5151 FBA A settings Fieldbus adapter A configuration.51.01 FBA A type Displays the type of the connected fieldbus adapter module.0 = Module is not found or is not properly connected, or isdisabled by parameter 50.01 FBA A enable; 1 = FPBA;32 = FCAN; 37 = FDNA; 101 = FCNA, 128 = FENA-11/21;135 = FENA-11; 135 = FECA; 136 = FEPL; 485 = FSCA.This parameter is read-only.-51.02 FBA A Par2 Parameters 51.02…51.26 are adapter module-specific. Formore information, see the documentation of the fieldbusadapter module. Note that not all of these parameters arenecessarily in use.-0…65535 Fieldbus adapter configuration parameter. 1 = 1… … … …51.26 FBA A Par26 See parameter 51.02 FBA A Par2. -0…65535 Fieldbus adapter configuration parameter. 1 = 151.27 FBA A par refresh Validates any changed fieldbus adapter moduleconfiguration settings. After refreshing, the value revertsautomatically to Done.Note: This parameter cannot be changed while the drive isrunning.DoneDone Refreshing done. 0Refresh Refreshing. 151.28 FBA A par table ver Displays the parameter table revision of the fieldbus adaptermodule mapping file (stored in the memory of the drive).In format axyz, where ax = major table revision number; yz =minor table revision number.This parameter is read-only.-Parameter table revision of adapter module. -51.29 FBA A drive typecodeDisplays the drive type code in the fieldbus adapter modulemapping file (stored in the memory of the drive).This parameter is read-only.-0…65535 Drive type code stored in the mapping file. 1 = 151.30 FBA A mapping fileverDisplays the fieldbus adapter module mapping file revisionstored in the memory of the drive in decimal format.This parameter is read-only.-0…65535 Mapping file revision. 1 = 151.31 D2FBA A commstatusDisplays the status of the fieldbus adapter modulecommunication.-Idle Adapter is not configured. 0Exec.init Adapter is initializing. 1Time out A timeout has occurred in the communication between theadapter and the drive.2Conf.err Adapter configuration error: mapping file not found in the filesystem of the drive, or mapping file upload has failed morethan three times.3Off-line Fieldbus communication is off-line. 4No. Name/Value Description Def/FbEq16