Name Type DescriptionSTART1 BOOLEAN Start signal from stage 1START2 BOOLEAN Start signal from stage 2P REAL Active PowerPPERCENT REAL Active power in % of calculated power base valueQ REAL Reactive powerQPERCENT REAL Reactive power in % of calculated power basevalue8.7.2.4 SettingsTable 123:GOPPDOP Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OnOpMode1 OffOverPower- - OverPower Operation mode 1Power1 0.0 - 500.0 % 0.1 1.0 Power setting for stage 1 in % ofcalculated power base valueAngle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for stage 1TripDelay1 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 1OpMode2 OffOverPower- - OverPower Operation mode 2Power2 0.0 - 500.0 % 0.1 1.0 Power setting for stage 2 in % ofcalculated power base valueAngle2 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for stage 2TripDelay2 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 2Table 124:GOPPDOP Group settings (advanced)Name Values (Range) Unit Step Default Descriptionk 0.00 - 0.99 - 0.01 0.00 Low pass filter coefficient for powermeasurement, U and ITable 125:GOPPDOP Non group settings (basic)Name Values (Range) Unit Step Default DescriptionGlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base ValuegroupsMode L1, L2, L3AronePos SeqL1L2L2L3L3L1L1L2L3- - Pos Seq Mode of measurement for current andvoltage1MRK 502 048-UEN A Section 8Current protection233Technical manual