9.2.5 SettingsTable 162:OV2PTOV Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OnOperationStep1 OffOn- - On Enable execution of step 1Characterist1 Definite timeInverse curve AInverse curve BInverse curve C- - Definite time Selection of time delay curve type for step1OpMode1 1 out of 32 out of 33 out of 3- - 1 out of 3 Number of phases required to operate (1of 3, 2 of 3, 3 of 3) from step 1U1> 1 - 200 %UB 1 120 Voltage start value (DT & IDMT) in % ofUBase for step 1t1 0.00 - 6000.00 s 0.01 5.00 Definite time delay of step 1t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curvesfor step 1k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delayfor step 1OperationStep2 OffOn- - On Enable execution of step 2OpMode2 1 out of 32 out of 33 out of 3- - 1 out of 3 Number of phases required to operate (1of 3, 2 of 3, 3 of 3) from step 2U2> 1 - 200 %UB 1 150 Voltage start value (DT & IDMT) in % ofUBase for step 2t2 0.000 - 60.000 s 0.001 5.000 Definite time delay of step 2Table 163:OV2PTOV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionGlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base ValuegroupsConnType PhN DFTPhN RMSPhPh DFTPhPh RMS- - PhN DFT Group selector for connection type9.2.6 Monitored dataTable 164:OV2PTOV Monitored dataName Type Values (Range) Unit DescriptionUL1 REAL - kV Voltage in phase L1UL2 REAL - kV Voltage in phase L2UL3 REAL - kV Voltage in phase L31MRK 502 048-UEN A Section 9Voltage protection265Technical manual