Name Type Default DescriptionBL_CLOSE BOOLEAN 0 Signal to block the close commandBL_UPD BOOLEAN 0 Steady signal for block of the position updatingPOSOPEN BOOLEAN 0 Signal for open position of apparatus from I/OPOSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/OTR_OPEN BOOLEAN 0 Signal for open position of truck from I/OTR_CLOSE BOOLEAN 0 Signal for close position of truck from I/ORS_CNT BOOLEAN 0 Resets the operation counterXIN BOOLEAN 0 Execution information from CSWITable 221:SXSWI Output signalsName Type DescriptionXPOS GROUP SIGNAL Group connection to CSWIEXE_OP BOOLEAN Executes the command for open directionEXE_CL BOOLEAN Executes the command for close directionOP_BLKD BOOLEAN Indication that the function is blocked for opencommandsCL_BLKD BOOLEAN Indication that the function is blocked for closecommandsUPD_BLKD BOOLEAN Update of position indication is blockedPOSITION INTEGER Apparatus position indicationOPENPOS BOOLEAN Apparatus open positionCLOSEPOS BOOLEAN Apparatus closed positionTR_POS INTEGER Truck position indicationCNT_VAL INTEGER Operation counter valueL_CAUSE INTEGER Latest value of the error indication during command12.2.4.2 SettingsTable 222:SXSWI Non group settings (basic)Name Values (Range) Unit Step Default DescriptiontStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus tomove after a commandtIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate positionAdaptivePulse Not adaptiveAdaptive- - Not adaptive Output resets when a new correct endposition is reachedtOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open commandtClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close commandSwitchType Load BreakDisconnectorEarthing SwitchHS Earthing Switch- - Disconnector 1=LoadBreak,2=Disconnector,3=EarthSw,4=HighSpeedEarthSwSuppressMidPos OffOn- - On Mid-position is suppressed during thetime tIntermediateSection 12 1MRK 502 048-UEN AControl342Technical manual