14.1.3 Setting guidelines SEMOD115063-294 v7The following settings are available for the Logic rotating switch for functionselection and LHMI presentation (SLGAPC) function:Operation: Sets the operation of the function On or Off.NrPos: Sets the number of positions in the switch (max. 32).OutType: Steady or Pulsed.tPulse: In case of a pulsed output, it gives the length of the pulse (in seconds).tDelay: The delay between the UP or DOWN activation signal positive front andthe output activation.StopAtExtremes: Sets the behavior of the switch at the end positions – if set toDisabled, when pressing UP while on first position, the switch will jump to the lastposition; when pressing DOWN at the last position, the switch will jump to the firstposition; when set to Enabled, no jump will be allowed.14.2 Selector mini switch VSGAPC SEMOD158754-1 v314.2.1 IdentificationSEMOD167850-2 v4Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberSelector mini switch VSGAPC - 4314.2.2 Application SEMOD158803-5 v9Selector mini switch (VSGAPC) function is a multipurpose function used in theconfiguration tool in PCM600 for a variety of applications, as a general purposeswitch. VSGAPC can be used for both acquiring an external switch position(through the IPOS1 and the IPOS2 inputs) and represent it through the single linediagram symbols (or use it in the configuration through the outputs POS1 andPOS2) as well as, a command function (controlled by the PSTO input), givingswitching commands through the CMDPOS12 and CMDPOS21 outputs.The output POSITION is an integer output, showing the actual position as aninteger number 0 – 3, where 0 = MidPos, 1 = Open, 2 = Closed and 3 = Error.An example where VSGAPC is configured to switch Autorecloser on–off from abutton symbol on the local HMI is shown in figure75. The I and O buttons on thelocal HMI are normally used for on–off operations of the circuit breaker.Section 14 1MRK 511 407-UEN CControl218 Phasor measurement unit RES670 2.2 IECApplication manual