IEC07000112-3-en.vsdPSTOCMDPOS12IPOS1NAM_POS1NAM_POS2IPOS2CMDPOS21OFFONVSGAPCSMBRRECONOFFSETONINTONEINVERTERINPUT OUTIEC07000112 V3 EN-USFigure 75: Control of Autorecloser from local HMI through Selector mini switchVSGAPC is also provided with IEC 61850 communication so it can be controlledfrom SA system as well.14.2.3 Setting guidelines SEMOD158807-4 v4Selector mini switch (VSGAPC) function can generate pulsed or steady commands(by setting the Mode parameter). When pulsed commands are generated, the lengthof the pulse can be set using the tPulse parameter. Also, being accessible on thesingle line diagram (SLD), this function block has two control modes (settablethrough CtlModel): Dir Norm and SBO Enh.14.3 Generic communication function for Double Pointindication DPGAPC SEMOD55384-1 v414.3.1 IdentificationGUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberGeneric communication function forDouble Point indicationDPGAPC - -14.3.2 Application SEMOD55391-5 v8Generic communication function for Double Point indication (DPGAPC) functionblock is used to send double point position indication to other systems, equipmentor functions in the substation through IEC 61850-8-1 or other communicationprotocols. It is especially intended to be used in the interlocking station-widelogics. To be able to get the signals into other systems, equipment or functions, onemust use other tools, described in the Engineering manual, and define which1MRK 511 407-UEN C Section 14ControlPhasor measurement unit RES670 2.2 IEC 219Application manual